Type TVR-Ex

For the control of variable air volume flows in potentially explosive atmospheres (ATEX)

Circular VAV terminal units for variable air volume systems, approved and certified for potentially explosive atmospheres (ATEX)

  • ATEX-compliant construction and parts
  • Approved for all gases, mists and vapours in zones 1 and 2, with electronic control additionally for dusts in zones 21 and 22
  • Suitable for the control of supply or extract air as well as for differential pressure control
  • Electronic or pneumatic control components
  • Closed blade air leakage to EN 1751, up to class 4
  • Casing air leakage to EN 1751, class C


Optional equipment and accessories

  • Spring return actuator
  • Auxiliary switch with adjustable switching points for capturing the end positions

VAV terminal unit Type TVR-Ex 00132058_0
  • Application
  • Description

Application

  • Circular EXCONTROL VAV terminal units of Type TVR-Ex for the precise supply air or extract air flow control in variable air volume systems
  • For use in potentially explosive atmospheres (ATEX)
  • Closed-loop volume flow control using an external power supply
  • Electronic or pneumatic volume flow control
  • Shut-off by means of switching (equipment supplied by others)

Special features

  • ATEX mark and certification
  • ATEX equipment group II, approved for use in zones 1 and 2; electronic control also for zones 21 and 22
  • Volume flow rate can later be measured and adjusted on site; configuration is possible using personal computer software

Classification

Electronic control: Equipment group II

  • Zones 1 and 2 (atmosphere: gases): II 2 G c II T5/T6
  • Zones 21 and 22 (atmosphere: dusts): II 2 D c II 80 °C


Pneumatic control: Equipment group II

  • Zones 1 and 2 (atmosphere: gases): II 2 G c II T5/T6

Nominal sizes

  • 125, 160, 200, 250, 315, 400

Construction

  • Galvanised sheet steel
  • P1: Inner duct powder-coated, silver grey (RAL 7001)
  • A2: Inner duct in stainless steel

Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Averaging differential pressure sensor for volume flow rate measurement
  • Damper blade
  • Connection for equipotential bonding
  • Cable bushings suitable for use in potentially explosive atmospheres
  • ATEX-compliant control components, factory assembled and complete with wiring and tubing
  • Aerodynamic functional testing on a special test rig prior to shipping of each unit
  • Unit carries test label with relevant data
  • High control accuracy (even with upstream bend R = 1D)

Attachments

  • Electronic control
  • Pneumatic control

Accessories

  • Actuator with auxiliary switch for capturing the end positions
  • Spring return actuator

Useful additions

  • Secondary silencer Type CA for demanding acoustic requirements

Construction features

  • Construction and materials comply with the EU directive and guidelines for use in potentially explosive atmospheres (ATEX)
  • Spigot with lip seal, for circular connecting ducts to EN 1506 or EN 13180

Materialien und Oberflächen

  • Gehäuse und Innenrohr aus verzinktem Stahlblech
  • Regelkomponenten aus Aluminiumdruckguss (Pneumatische Regelung: Kunststoff)
  • Gleitlager aus Kunststoff
  • Stellklappe aus Edelstahl mit Dichtung aus Kunststoff TPE
  • Differenzdrucksensor aus Aluminium
  • P1: luftführendes Innenrohr mit Pulverbeschichtung
  • A2: luftführendes Innenrohr aus Edelstahl

Standards and guidelines

  • Directive 94/9/EC: Equipment and protective systems intended for use in potentially explosive atmospheres
  • Closed blade air leakage to EN 1751, class 4 (nominal sizes 125 and 160, class 3).
  • Nominal sizes 125 and 160 meet the general requirements, nominal sizes 200 – 400 meet the increased requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage
  • Casing air leakage to EN 1751, class C

Maintenance

  • Maintenance-free as construction and materials are not subject to wear


Electronic control

  • Zero point correction of the static differential pressure transducer should be carried out once per year (recommendation)

Technical information

Function, Technical data, Quick sizing, Specification text, Order code, Produktbeziehungen

  • Function
  • Technical data
  • Quick sizing
  • Specification text
  • Order code

Functional description

The VAV terminal unit is fitted with a differential pressure sensor for measuring the volume flow rate.

The control components (attachments) include a differential pressure transducer that transforms the differential pressure (effective pressure) into an electric signal, a controller, and an actuator.

For most applications, the setpoint value comes from a room temperature controller which is installed outside of the potentially explosive atmosphere.

The controller compares the actual value with the setpoint value and alters the control signal of the damper actuator if there is a difference between the two values.

The connections for the supply voltage and for the voltage signals are made in a terminal box that is suitable for use in potentially explosive atmospheres.

Volumenstrombereiche

Die Mindestdruckdifferenz der VVS-Regelgeräte ist eine wichtige Größe zur Planung des Kanalnetzes und zur Dimensionierung des Ventilators einschließlich der Drehzahlsteuerung.

Es muss sichergestellt sein, dass unter allen Betriebsbedingungen an allen Regelgeräten ein ausreichender Kanaldruck ansteht. Der Messpunkt oder die Messpunkte für die Drehzahlsteuerung des Ventilators sind dementsprechend auszuwählen.

Die Volumenstrombereiche von VVS-Regelgeräten sind von der Nenngröße und von der verwendeten Regelkomponente (Anbauteil) abhängig. Die dargestellten Tabellenwerte sind die Minimal- und Maximalwerte des VVS-Regelgerätes. Für bestimmte Regelkomponenten gelten eingeschränkte Bereiche. Dies gilt insbesondere für Regelkomponenten mit statischem Differenzdrucktransmitter. Volumenstrombereiche für alle Regelkomponenten enthält das Auslegungsprogramm Easy Procuct Finder.

Nominal sizes

125 – 400 mm

Volume flow rate range

15 – 1680 l/s or 54 – 6048 m³/h

Volume flow rate control range

Approx. 15 to 100 % of the nominal volume flow rate

Maximum differential pressure

1000 Pa

Operating temperature

10 – 50 °C


Elektronisch

Versorgungsspannung (Wechselspannung)

24 V AC ± 10 %, 50/60 Hz

Versorgungsspannung (Gleichspannung)

24 V DC ± 10 %

Anschlussleistung (Wechselspannung)

Max. 20 VA

Anschlussleistung (Gleichspannung)

Max. 20 W

Eingang Sollwertsignal

0 – 10 V DC, Ra > 100 kΩ

Ausgang Istwertsignal

0 – 10 V DC, max. 0,5 mA

Schutzklasse

III (Schutzkleinspannung)

Schutzgrad

IP 42

EG-Konformität

ATEX nach 94/9/EG, EMV nach 2004/108/EG, Niederspannung nach 2006/95/EG


Pneumatisch

Betriebsdruck

1,3 bar ± 0,1 bar

Luftverbrauch Volumenstromregelung

50 ln/h

Luftverbrauch Druck-Volumenstrom-Kaskade

100 ln/h

Steuerdruck

0,2 – 1,0 bar

Maximal zulässiger Druck

1,5 bar

Druckluft

öl-, wasser- und staubfreie Instrumentendruckluft

Schutzgrad

IP 42






Die Schnellauslegung gibt einen guten Überblick über die zu erwartenden Schalldruckpegel im Raum. Ungefähre Zwischenwerte können interpoliert werden. Zu exakten Zwischenwerten und Spektraldaten führt die Auslegung mit unserem Auslegungsprogramm Easy Product Finder.

Die Auswahl der Nenngröße erfolgt zunächst nach den gegebenen Volumenströmen Vmin und Vmax. In der Schnellauslegung sind praxisgerechte Dämpfungswerte berücksichtigt. Liegt der Schalldruckpegel über dem zulässigen Wert, sind ein größeres Volumenstrom-Regelgerät und/oder ein Schalldämpfer erforderlich.

TVR-Ex, electronic, Sound pressure level at differential pressure 150 Pa

Nominal size V Air-regenerated noise Case-radiated noise
Nominal size V
Nominal size V LPA LPA1 LPA2
Nominal size l/s m³/h dB(A)

125

22

79

36

25

16

<15

16

125

60

216

45

36

30

28

25

125

105

378

49

40

34

32

31

125

150

540

52

41

34

32

35

160

35

126

41

30

22

19

22

160

100

360

47

39

34

31

28

160

175

630

50

42

37

34

32

160

250

900

53

44

39

36

37

200

60

216

41

32

24

22

21

200

160

576

47

40

34

33

29

200

280

1008

50

44

40

38

32

200

405

1458

54

45

39

38

38

250

90

324

38

30

24

22

22

250

245

882

47

40

34

32

35

250

430

1548

48

42

38

37

37

250

615

2214

52

44

38

37

42

315

145

522

43

36

29

26

29

315

410

1476

47

42

35

34

39

315

720

2592

49

44

39

38

42

315

1030

3708

53

48

42

41

46

400

240

864

43

36

29

26

31

400

670

2412

44

38

32

30

37

400

1175

4230

47

42

36

35

41

400

1680

6048

50

44

38

37

46

① TVR-Ex

② TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 500 mm

③ TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1000 mm

④ TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1500 mm


TVR-Ex, pneumatic, Sound pressure level at differential pressure 150 Pa

Nominal size V Air-regenerated noise Case-radiated noise
Nominal size V
Nominal size V LPA LPA1 LPA2
Nominal size l/s m³/h dB(A)

125

15

54

33

22

<15

<15

<15

125

40

144

39

29

22

19

20

125

70

252

46

37

31

29

26

125

100

360

49

40

34

32

31

160

25

90

40

28

20

16

20

160

75

270

45

35

29

26

25

160

125

450

49

41

36

33

29

160

175

630

50

42

37

34

32

200

40

144

40

31

23

20

20

200

125

450

46

37

31

30

26

200

210

756

48

41

36

35

30

200

300

1080

51

44

40

38

33

250

60

216

41

32

24

22

21

250

200

720

44

36

31

29

30

250

340

1224

47

40

35

34

36

250

475

1710

49

42

38

37

38

315

105

378

42

35

28

25

28

315

330

1188

45

40

33

31

35

315

555

1998

47

42

36

35

40

315

775

2790

50

44

39

38

43

400

170

612

43

36

30

26

30

400

545

1962

43

37

31

29

35

400

920

3312

45

40

34

33

39

400

1300

4680

48

42

37

35

43

① TVR-Ex

② TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 500 mm

③ TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1000 mm

④ TVR-Ex with secondary silencer CA, insulation thickness 50 mm, length 1500 mm


VAV terminal units for variable and constant air volume systems in potentially explosive atmospheres, suitable for supply or extract air, available in 6 nominal sizes.

High control accuracy (even with upstream bend R = 1D).

Ready-to-commission unit which consists of the mechanical parts, the electronic control components, and parts for equipotential bonding and for use in potentially explosive atmospheres. Each unit contains an averaging differential pressure sensor for volume flow rate measurement and a damper blade.

Factory-assembled control components complete with wiring and tubing.

Differential pressure sensor with 3 mm measuring holes (resistant to dust and pollution)

Spigot with lip seal, for circular connecting ducts to EN 1506 or EN 13180.

Closed blade air leakage to EN 1751, class 4 (nominal sizes 125 and 160, class 3).

Casing air leakage to EN 1751, class C.

Special features

  • ATEX mark and certification
  • ATEX equipment group II, approved for use in zones 1 and 2; electronic control also for zones 21 and 22
  • Volume flow rate can later be measured and adjusted on site; configuration is possible using personal computer software

Materialien und Oberflächen

  • Gehäuse und Innenrohr aus verzinktem Stahlblech
  • Regelkomponenten aus Aluminiumdruckguss (Pneumatische Regelung: Kunststoff)
  • Gleitlager aus Kunststoff
  • Stellklappe aus Edelstahl mit Dichtung aus Kunststoff TPE
  • Differenzdrucksensor aus Aluminium
  • P1: luftführendes Innenrohr mit Pulverbeschichtung
  • A2: luftführendes Innenrohr aus Edelstahl

Construction

  • Galvanised sheet steel
  • P1: Inner duct powder-coated, silver grey (RAL 7001)
  • A2: Inner duct in stainless steel

Technical data

  • Nominal sizes: 125 to 400 mm
  • Volume flow rate range: 15 to 1680 l/s or 54 to 6048 m³/h
  • Volume flow rate control range: approx. 15 – 100 % of the nominal volume flow rate
  • Maximum differential pressure: 1000 Pa

Attachments

Variable volume flow control with electronic controller to switch a control signal and an actual value signal for integration into the central BMS.

  • Supply voltage 24 V AC
  • Supply voltage for actuator: 230 V AC
  • Signal voltages 0 – 10 V DC
  • The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
  • Volume flow rate control range: approx. 15 – 100 % of the nominal volume flow rate
  • Actuator with adjustable running time, 7.5 – 120 s

Sizing data

  • V _______________________ [m³/h]
  • Δpst _______________________ [Pa]

Air-regenerated noise

  • LPA _______________________ [dB(A)]

Case-radiated noise

  • LPA _______________________ [dB(A)]

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.

00107034_0.

 Type
TVR-Ex       VAV terminal unit for use in potentially explosive atmospheres

 Material
       No entry: galvanised sheet steel
P1       Inner duct powder-coated, silver grey (RAL 7001)
A2       Inner duct in stainless steel

Nominal size [mm]
125
160
200
250
315
400

 

 Attachments (control component)
       For example
       Electronic control
S1S       Internal controller and actuator
       Pneumatic control
PG5       Volume flow controller with actuator
PJ5       Pressure and volume flow cascade (±20 Pa)

 Operating values [m³/h or l/s, Pa]
       Electronic control
       Vmin – Vmax
       Pneumatic control
       Volume flow rate Vmin – Vmax
       Pressure and volume flow cascade       Vmin – Vmax / Δpsetpoint

 Damper blade position
       Only for spring return actuators and pneumatic actuators
NO       Pressure off/power off to OPEN
NC       Power off/Pressure off to close

 

Variants, Attachments, Dimensions and weight

  • Attachments
  • Dimensions and weight

TVR-Ex, EXCONTROL Electric control components

Order code detail Control function Controller Differential pressure transducer Actuator

Internal controller





S1S

Volume flow rate

Universal controller (use in areas with potentially explosive atmospheres) Schischek

Static, integral

Actuator

S1F

Volume flow rate

Universal controller (use in areas with potentially explosive atmospheres) Schischek

Static, integral

Spring return actuator

S1X

Volume flow rate

Universal controller (use in areas with potentially explosive atmospheres) Schischek

Static, integral

Actuator with auxiliary switches

S1Y

Volume flow rate

Universal controller (use in areas with potentially explosive atmospheres) Schischek

Static, integral

Spring return actuator with auxiliary switch

External controller





TES

Volume flow rate

Volume flow rate controller TCU3 (use in areas with potentially explosive atmospheres) TROX/Schischek

Static

Actuator

TEF

Volume flow rate

Volume flow rate controller TCU3 (use in areas with potentially explosive atmospheres) TROX/Schischek

Static

Spring return actuator

TEX

Volume flow rate

Volume flow rate controller TCU3 (use in areas with potentially explosive atmospheres) TROX/Schischek

Static

Actuator with auxiliary switches

TEY

Volume flow rate

Volume flow rate controller TCU3 (use in areas with potentially explosive atmospheres) TROX/Schischek

Static

Spring return actuator with auxiliary switch


TVR-Ex, EXCONTROL Pneumatic control components

Order code detail Control function Controller Differential pressure transducer Actuator

Volume flow controllers





PG5

Volume flow rate

Volume flow controller Sauter

Integral

Actuator

Pressure and volume flow cascade





PJ5

Room pressure

Room pressure controller ± 20 Pa Volume flow controller Sauter

Integral

Actuator

PL5

Room pressure

Room pressure controller ± 50 Pa Volume flow controller Sauter

Integral

Actuator


Anbauteile: VARYCONTROL Regelkomponenten

Regel- größe Schnittstelle Vmin -/ Vmax - Verstellung Differenzdruck- transmitter Stellantrieb Fabrikat LVC TVR TVJ TVT TZ-S TA-S TVZ TVA TVM TVRK TVLK





















Easyregler


Dynamisch















Easy

V



Integriert

Integriert







Compactregler


Dynamisch















BC0

V

MP-Bus


Integriert

Integriert





BF0

V

MP-Bus


Integriert

Integriert












BL0

V

LonWorks


Integriert

Integriert






BM0

V

Modbus


Integriert

Integriert













BM0-J6

V

Modbus und steckerfertiger Anschlussleitung


Integriert

Integriert













XG0

V



Integriert

Integriert












XB0

V



Integriert

Integriert






LN0

V



Integriert

Integriert






LK0

V

KNX
















LY0

V



Integriert

Integriert














Compactregler


Statisch















SA0

V



Integriert

Integriert













SC0

Δp



Integriert

Schnelllaufender Stellantrieb integriert















Universalregler


Dynamisch















B11

V



Integriert

Stellantrieb, Drehmoment für TVT












B13

V



Integriert

Stellantrieb







B27

V



Integriert

Stellantrieb












B1B

V



Integriert

Federrücklaufantrieb






XC3

V



Integriert

Federrücklaufantrieb








Universalregler


Statisch















BP1

V

MP-Bus


Separates Bauteil

Stellantrieb, Drehmoment für TVT












BP3

V

MP-Bus


Separates Bauteil

Stellantrieb





BPB

V

MP-Bus


Separates Bauteil

Federrücklaufantrieb





BPG

V

MP-Bus


Separates Bauteil

Schnelllaufender Stellantrieb




BB1

V



Separates Bauteil

Stellantrieb, Drehmoment für TVT












BB3

V



Separates Bauteil

Stellantrieb





BBB

V



Separates Bauteil

Federrücklaufantrieb






XD1

V



Integriert

Stellantrieb





XD3

V



Integriert

Federrücklaufantrieb





BR1

Δp

MP-Bus


100 Pa

Stellantrieb, Drehmoment für TVT












BR3

Δp

MP-Bus


100 Pa

Stellantrieb






BRB

Δp

MP-Bus


100 Pa

Federrücklaufantrieb





BRG

Δp

MP-Bus


100 Pa

Schnelllaufender Stellantrieb







BS1

Δp

MP-Bus


600 Pa

Stellantrieb, Drehmoment für TVT












BS3

Δp

MP-Bus


600 Pa

Stellantrieb









BSB

Δp

MP-Bus


600 Pa

Federrücklaufantrieb









BSG

Δp

MP-Bus


600 Pa

Schnelllaufender Stellantrieb









BG1

Δp



100 Pa

Stellantrieb, Drehmoment für TVT












BG3

Δp



100 Pa

Stellantrieb






BGB

Δp



100 Pa

Federrücklaufantrieb





BH1

Δp



600 Pa

Stellantrieb, Drehmoment für TVT












BH3

Δp



600 Pa

Stellantrieb










BHB

Δp



600 Pa

Federrücklaufantrieb









XE1

Δp



Integriert, 100 Pa

Stellantrieb





XE3

Δp



Integriert, 100 Pa

Federrücklaufantrieb





XF1

Δp



Integriert, 600 Pa

Stellantrieb









XF3

Δp



Integriert, 600 Pa

Federrücklaufantrieb









① TROX, ② TROX/Belimo, ③ TROX/Gruner, ④ Sauter, ⑤ Siemens

☒ Bestellschlüsseldetail, V Volumenstrom, Δp Differenzdruck


Anbauteile: LABCONTROL Regelkomponenten

Regel- größe Schnittstelle Vmin -/ Vmax - Verstellung Differenzdruck- transmitter Stellantrieb TVR TVJ TVT TZ-S TA-S TVZ TVA TVRK TVLK


















Easylabregler


Statisch












Elab

Raumzuluft

Raumabluft

Raumdruck

Einzelregler

TCU3


Integriert

Schnelllaufender Stellantrieb








Elab

Raumzuluft

Raumdruck

Einzelregler

TCU3


Integriert

Schnelllaufender Stellantrieb









Elab

Raumabluft

Raumdruck

Einzelregler

TCU3


Integriert

Schnelllaufender Stellantrieb









Elab

Raumzuluft

Raumabluft

Raumdruck

Laborabzug

Einzelregler

TCU3


Integriert

Schnelllaufender Stellantrieb











Elektronischer Regler


Statisch












TMA

Raumzuluft

Raumabluft

Raumdruck


TCU-LON-II mit LonWorks-Schnittstelle

Integriert

Schnelllaufender Stellantrieb








TMB

Schnelllaufender Stellantrieb (bürstenloser Motor)








TMA

Raumzuluft

Raumdruck


TCU-LON-II mit LonWorks-Schnittstelle

Integriert

Schnelllaufender Stellantrieb









TMB

Schnelllaufender Stellantrieb (bürstenloser Motor)









TMA

Raumabluft

Raumdruck


TCU-LON-II mit LonWorks-Schnittstelle

Integriert

Schnelllaufender Stellantrieb









TMB

Schnelllaufender Stellantrieb (bürstenloser Motor)









TMA

Raumzuluft

Raumabluft

Raumdruck

Laborabzug


TCU-LON-II mit LonWorks-Schnittstelle

Integriert

Schnelllaufender Stellantrieb









TMB

Schnelllaufender Stellantrieb (bürstenloser Motor)













Installation details, Basic information and nomenclature

  • Installation details
  • Basic information and nomenclature

Installation and commissioning

  • Connections for equipotential bonding: Suitable cables must be connected by others


Electronic control

  • Any installation orientation
  • Zero point correction required


Pneumatic control

  • Installation orientation must be as shown on the sticker

Anströmbedingungen

Die Volumenstromgenauigkeit ΔV gilt für gerade Anströmung. Formstücke wie Bögen, Abzweige oder Querschnittsveränderungen verursachen Turbulenzen, die die Messung beeinflussen können. Bei Ausführung von Luftleitungsanschlüssen, wie z. B. dem Abzweig von einer Hauptleitung, ist die EN 1505 zu beachten. Für manche Einbausituationen sind gerade Anströmlängen erforderlich.

Platzbedarf für Inbetriebnahme und Instandhaltung

Um die Arbeiten zur Inbetriebnahme und Instandhaltung zu ermöglichen, ausreichenden Bauraum im Bereich der Anbauteile freihalten. Gegebenenfalls sind Revisionsöffnungen in ausreichender Größe erforderlich, sodass die Anbauteile leicht zugänglich sind.

Space required

Nominal size
Nominal size mm

125

600

220

300

160

600

220

300

200

600

310

300

250

600

310

300

315

600

460

300

400

600

460

300


Principal dimensions

ØD [mm]

VAV terminal units made of stainless steel: Outside diameter of the spigot

VAV terminal units made of plastic: Inside diameter of the connecting spigot

ØD₁ [mm]

Pitch circle diameter of flanges

ØD₂ [mm]

Outside diameter of flanges

ØD₄ [mm]

Inside diameter of the screw holes of flanges

L [mm]

Length of unit including connecting spigot

L₁ [mm]

Length of casing or acoustic cladding

B [mm]

Duct width

B₁ [mm]

Screw hole pitch of flange (horizontal)

B₂ [mm]

Outside dimension of flange (width)

B₃ [mm]

Width of device

H [mm]

Duct height

H₁ [mm]

Screw hole pitch of flange (vertical)

H₂ [mm]

Outside dimension of flange (height)

H₃ [mm]

Unit height

n [ ]

Number of flange screw holes

T [mm]

Flange thickness

m [kg]

Unit weight including the minimum required attachments (e.g. Compact controller)

Acoustic data

fm [Hz]

Octave band centre frequency

LPA [dB(A)]

A-weighted sound pressure level of air-regenerated noise of the VAV terminal unit, system attenuation taken into account

LPA1 [dB(A)]

A-weighted sound pressure level of air-regenerated noise of the VAV terminal unit with secondary silencer, system attenuation taken into account

LPA2 [dB(A)]

A-weighted sound pressure level of case-regenerated noise of the VAV terminal unit, system attenuation taken into account

LPA3 [dB(A)]

A-weighted sound pressure level of case-regenerated noise of the VAV terminal unit with acoustic cladding, system attenuation taken into account


All sound pressure levels are based on 20 μPa.

Volume flow rates

Vnom [m³/h] and [l/s]

Nominal volume flow rate (100 %)

  • The value depends on product type and nominal size
  • Values are published on the internet and in technical leaflets, and stored in the Easy Product Finder design software.
  • Reference value for calculating percentages (e.g. Vmax)
  • Upper limit of the setting range and maximum volume flow rate setpoint value for the VAV terminal unit

Vmin unit [m³/h] and [l/s]

Technically possible minimum volume flow rate

  • The value depends on product type, nominal size and control component (attachment)
  • Values are stored in the Easy Product Finder design software
  • Lower limit of the setting range and minimum volume flow rate setpoint value for the VAV terminal unit
  • Depending on the controller, setpoint values below Vmin unit (if Vmin equals zero) may result in unstable control or shut-off

Vmax [m³/h] and [l/s]

Upper limit of the operating range for the VAV terminal unit that can be set by customers

  • Vmax can only be smaller than or equal to Vnom
  • In case of analog signalling to volume flow controllers (which are typically used), the set maximum value (Vmax) is allocated to the setpoint signal maximum (10 V) (see characteristic)

Vmin [m³/h] and [l/s]

Lower limit of the operating range for the VAV terminal unit that can be set by customers

  • Vmin should be smaller than or equal to Vmax
  • Do not set Vmin smaller than Vmin unit, otherwise the control may become unstable or the damper blade may close
  • Vmin may equal zero
  • In case of analog signalling to volume flow controllers (which are typically used), the set minimum value (Vmin) is allocated to the setpoint signal minimum (0 or 2 V) (see characteristic)

V [m³/h] and [l/s]

Volume flow rate

ΔV [± %]

Volume flow rate tolerance from setpoint value

ΔVwarm [± %]

Volume flow rate tolerance for the warm air flow of dual duct terminal units

Differential pressure

Δpst [Pa]

Static differential pressure

Δpst min [Pa]

Static differential pressure, minimum

  • The static minimum differential pressure is equal to the pressure loss of the VAV terminal unit when the damper blade is open, caused by flow resistance (sensor tubes, damper mechanism)
  • If the pressure on the VAV terminal unit is too low, the setpoint volume flow rate may not be achieved, not even when the damper blade is open
  • Important factor in designing the ductwork and in rating the fan including speed control
  • Sufficient duct pressure must be ensured for all operating conditions and for all terminal units, and the measurement point or points for speed control must have been selected accordingly to achieve this

Ausführungen

Verzinktes Stahlblech

  • Luftführendes Gehäuse aus verzinktem Stahlblech
  • Im Luftstrom befindliche Teile, wie bei der Serie beschrieben
  • Außenliegende Bauteile, beispielsweise Konsolen und Deckel, in der Regel aus verzinktem Stahlblech

Pulverbeschichtete Oberfläche (P1)

  • Luftführendes Gehäuse aus verzinktem Stahlblech, pulverbeschichtet RAL 7001, silbergrau
  • Im Luftstrom befindliche Teile pulverbeschichtet oder Kunststoff
  • Fertigungsbedingt eventuell einige im Luftstrom liegende Teile aus Edelstahl oder Aluminium pulverbeschichtet
  • Außenliegende Bauteile, beispielsweise Konsolen und Deckel, in der Regel aus verzinktem Stahlblech

Edelstahl (A2)

  • Luftführendes Gehäuse aus Edelstahl Typ 1.4201
  • Im Luftstrom befindliche Teile pulverbeschichtet oder Edelstahl
  • Außenliegende Bauteile, beispielsweise Konsolen und Deckel, in der Regel aus verzinktem Stahlblech

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.


Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265